Click on image(s) to enlarge
Dual display controller, 48 x 48mm fascia, universal input with up to 4 outputs. Single analogue input configurable for up to 18 different sensors/signals. 2-4 Outputs configurable as
relays (also as Open/Close logic for motorised valve control), SSR,
4-20mA, 0-10V signal (both for control or re-scalable retransmission
of process/setpoint).
The switch mode power supply, with extended range
24-230Vac/Vdc, does not require any jumpers setting.
Control modes: On/Off, PID + Autotuning, Heating/Cooling PID with
neutral zone.
Software features include the launch Tuning and the selection of 2-4
setpoints by digital input, the optional manual reset of output by
frontal keyboard ("Limit controller"), Latch-on function for sensors
calibration (including load cells), a programmable cycle of 3 steps .
Optional features are the serial communication RS485-ModbusRTU and load
monitoring function (Loop Break Alarm) with current transformer
TA.
Sealing IP65 with frontal gasket.
Optional Memory Card to copy all parameters, available also with
internal battery therefore not requiring to power up the unit.
Software
application LABSOFTVIEW for Windows enables setting and monitoring of
parameters on PC.
UL-CSA approved for North-American market.
Technical
data
- SIZE: 48 x 48 (fascia) x 122.5mm (deep)
-
SUPPLY: 24-230 Vac / Vdc +/- 15% 50/60Hz
-
CONSUMPTION: 3W
-
DISPLAY: dual 4 digits, 8 red LEDs, decimal point
-
OPERATING CONDITIONS: 0-45°C, 35..95rH%
-
INPUTS: 1 configurable TC K, J, S, R, PT100 (2ranges), NI100, PT1000, PT500, PTC1K, NTC10K,0-10V, 0/4-20mA, 0-40mV, Potentiometer 6KΩ / 150KΩ, TA 50mA.
-
OUTPUTS
-
ATR243-20ABC : 2 relays 5A resistive OR 1 relay + 1 logic SSR 12V-30mA
/ 4..20mA / 0...10Volt for control or retransmission (4000 points
accuracy)
-
ATR243-21ABC-T : 2 relays 5A resistive + 1 logic SSR 12V-30mA / 4..20mA
/ 0...10Volt for control or retransmission (4000 points accuracy) +
RS485 Modbus RTU (57600 baud max) + Input TA 50ma for Loop Break Alarm
-
ATR243-31ABC : 3 relays 5A resistive + 1 logic SSR 12V-30mA / 4..20mA /
0...10Volt for control or retransmission (4000 points accuracy) + Input
TA 50ma for Loop Break Alarm
-
DIGITAL INPUT: Tuning Start, Setpoint change, selection Man/Auto, Hold function, Start/Stop pre-programmed cycle
-
CONTROL MODES: ON/OFF, P, PI, PID, Autotuning
-
ACCURACY: 0.5% ±1digit for TC/RTD; 0.2%±1digit for V/mA
-
SAMPLING TIME: selectable (max 15ms)
-
SEALING: IP54 Frontal (IP65 with gasket), IP30 Box, IP20 Terminal blocks
-
CONFIGURATION: Parameters protected by password, Memory card with
battery for serial productions, software for parameters settings on PC.
-
CERTIFICATIONS : CE CSA UL

Click to download the PIXSYS ATR243 Operating & Installation Manual
See Also :
Model 1: ATR243-20ABC : 2 relays 5A resistive OR 1 relay + 1 logic SSR 12V-30mA
/ 4..20mA / 0...10Volt for control or retransmission (4000 points
accuracy)
Model 2: ATR243-21ABC-T : 2 relays 5A resistive + 1 logic SSR 12V-30mA / 4..20mA
/ 0...10Volt for control or retransmission (4000 points accuracy) +
RS485 Modbus RTU (57600 baud max) + Input TA 50ma for Loop Break Alarm
Model 3: ATR243-31ABC : 3 relays 5A resistive + 1 logic SSR 12V-30mA / 4..20mA /
0...10Volt for control or retransmission (4000 points accuracy) + Input
TA 50ma for Loop Break Alarm